Brand Name : ESTEL
Model Number : EL215-APNRF
Certification : ISO9001, CE, 3C, FCC, TLC
Place of Origin : Shenzhen, China (Mainland)
MOQ : 1
Price : 358-2143 usd
Payment Terms : L/C, D/A, D/P, T/T, Western Union
Supply Ability : 20,000 sets per month
Delivery Time : 7-10 working days
Packaging Details : carton/wooden case
System Rated Capacity : 215kWh
Battery Cluster Configuration Method : 1P15S
Rated Charge/Discharge Power : 100kW
DC Voltage Range : 672-864V
Grid Side Voltage Range : AC400V±10%
Inverter Operating Mode : Three-phase three-wire grid- connected operation
Table 1 Main Technical Parameters Table
| NO: | Item Description | Specification | Notes |
| 1 | System Rated Capacity | 215kWh | |
| 2 | Battery Cluster Configuration Method | 1P15S | |
| 3 | Rated Charge/Discharge Power | 100kW | Overload capacity: 110% |
| 4 | DC Voltage Range | 672-864V | |
| 5 | Grid Side Voltage Range | AC400V±10% | |
| 6 | Inverter Operating Mode | Three-phase three-wire grid- connected operation | |
| 7 | Operating Mode | Grid-connected operation | |
| 8 | System Efficiency | ≥85% | AC side@25± 2℃ 0.5P |
| 9 | Power Factor | -1~1 | Adjustable |
| 10 | Rated Charge/Discharge | 0.5P | |
| 11 | Storage Temperature Range | -30℃~60℃ | |
| 12 | Permitted Operating Temperature Range | Discharge:-20~55℃ ; Charge:0~55℃ | |
| 13 | Best Operating Temperature Range | 25±2℃ | |
| 14 | System Cycle Life | ≥6000 t i m e s | @25±2℃ , 0.5P,EOL≥80% |
| 15 | Relative Humidity | RH ≤95% | No condensation |
| 16 | Altitude | ≤3000m | >3000m@90% >4000m@8 0%Reduce rated power |
| 17 | Protection Grade | IP54 | |
| 18 | Cabinet Dimensions (W*H*D) | Approx. 2100*2300*1200 ( mm) | |
| 19 | Weight | Approx. 2850kg | |
| 20 | External Communication | Ethernet, wireless 4G | |
| 21 | Protection Grade | IP54 | |
| 22 | Anti-corrosion Grade | Not less than C3 | |
| 23 | System Design Life | ≥10 years | |
|
24 |
External Electrical Interface | AC input: three-phase four wire+PE AC output: three-phase four Photovoltaic input: Two channels | Note: Need to connect the N phase from the grid side to the N row in the cabinet to provide AC220V auxiliary power for the cabinet |




|
|
Telecom Power System Offering 100kW Rated Charge and Discharge Power with Advanced Control and Operation Software System Images |